Illustrated here is our batchTREAT BT40 pH Neutralization System
System Performance Specifications: | Influent Characteristic:
Flow 0-200 GPM, 40
GPM average / 2400 GPH max. Influent pH: 0 < pH < 14.
Temperature 32-140F. (High temp units available for
temperatures up to 212F. Effluent pH Range: typical 6.5 < pH < 8.5 (note: the effluent pH range is fully programmable through the operator interface). Effluent Monitoring: As mandated by the local controlling authority and by most discharge permits continuous monitoring of effluent flow and pH is provided on a circular chart recorder, paperless recorder, or via a data logger. Additionally SCADA systems are available with automatic report generation. |
The batchTREAT family of pH Adjustment Systems are small,
compact, packaged pH neutralization systems designed to
neutralize acidic and alkaline wastewater discharges from
any source. The pH neutralization system displayed here is the smallest of our batchTREAT family of pH systems and is capable of treating wastewater flows of up to 40 GPM continuous and 160 GPM intermittent. With the use of an influent equalization system, which is standard on all of our pH systems, periodic flows in excess of 200 GPM can be handled. The batchTREAT family of pH neutralization systems are well suited to neutralize wastewater streams from any source including highly acidic or highly alkaline effluent streams. |
|
Utilities, Weight, Dimensions: | Electrical: 480VAC,
3 phase, 60 Hz, 20 amp.
Disconnect not required (a disconnect is provided on our
MCP). Air: Less than 1 SCFH @ 80 psig. Dimensions: 44" x 84" x 72"(H) - Not including the optional influent equalization system. Weight: Approx. 3000 lbs. dry (not including shipping crate). |
All of our pH neutralization systems are supplied as
complete "turnkey" packages. Prior to shipping all plumbing
and electrical connections are complete and the neutralization system
undergoes extensive burn in testing in our QC area including
a wet / hydro test. The Main Control Panel (MCP) is equipped with a main disconnect providing OSHA Lock Out / Tag Out (LOTO) and UL 508 compliance. Electrical requires a single point connection. All of our pH adjustment systems utilize a fail safe valve on the discharge that immediately halts flow in the event of a discharge contravention, alarm or a loss of power. This valve requires a small air supply. If air is not available the same function is provided in an all electric configuration. |
|
Construction: | Tanks: PP, PE,
XLPE, FRP, and all stainless alloys. Pipe, Valves, and Fittings: PVC, CPVC, PP, PE, PVDF, and all stainless alloys. Main Control Panel: All of our pH systems are controlled by an programmable logic controller (PLC) typically Allen-Bradley. All panels are built to NEC, UL 508 and OSHA standards. Weight: Approx. 3000 lbs. dry (not including shipping crate). |